Quick answer: The Building Code does not require heat recovery ventilation in a new Auckland home, because opening windows plus ducted extract fans meet G4/AS1, though BRANZ recommends mechanical ventilation as the default way to get enough fresh air.
Somewhere between the concept sketch and the consent drawings, someone will ask whether your new home or extension should have a whole-house ventilation system. A supplier mentions heat recovery. Your builder says windows and fans pass consent. Both are right, which is exactly why the question is hard to settle.
The decision lands early because it changes the plans. A heat recovery unit needs somewhere to live, ducts need a route through the ceiling, and the fresh-air intake has to sit away from the bins and the neighbour’s rangehood outlet. Leave it until the frame is up and the system goes where it fits, not where it works.
Our design team at Sonder Architecture settles this question on new homes and extensions across Auckland, and the honest answer starts with how little the Code asks for.
What the Building Code requires for ventilation in a new home
Clause G4 in plain terms
The Building Code is the set of performance rules every building in New Zealand must meet, and clause G4 is the one about fresh air. Its stated objective is to protect people from illness or loss of amenity caused by a lack of fresh air. The main performance line, clause G4.3.1 of the Building Regulations 1992, says spaces inside a building must have a means of ventilation with outdoor air that provides enough air changes to keep the air pure.
G4 goes further than fresh air. Buildings must have a way to collect or remove cooking fumes and odours, moisture from bathing, showering and laundry, and products of combustion from the spaces where they’re made. Mechanical air-handling systems must be built and maintained so bacteria, pathogens and allergens don’t multiply inside them. And where a fixed fire or gas appliance draws its air from the room, the ventilation must supply that extra air too.
Notice what G4 doesn’t say. It names no system, no product and no airtightness level. It sets the outcome and leaves the method to the designer.
The acceptable solution: windows plus extract fans
Because a performance rule is hard to check, MBIE publishes acceptable solutions: ready-made methods that a council must accept as proof of compliance. Under section 19 of the Building Act 2004, a building consent authority (in Auckland, the council) must accept compliance with an acceptable solution as establishing compliance with the Code. For ventilation, that document is G4/AS1, now in its fifth edition, published on 28 July 2025. MBIE’s information sheet on the change says the fourth edition could be used only until 31 July 2026, so a design lodged today is checked against the fifth.
G4/AS1 lets you ventilate a house naturally, mechanically, or with a mix of the two. The natural route is the one most new homes use. Each occupied space needs opening windows or other openings to the outside with a net openable area of at least 5% of its floor area, and any space with a cooktop, shower or bath also needs a mechanical extract fan: at least 25 litres per second (L/s) for showers and baths, and 50 L/s for cooktops. Litres per second is simply how much air the fan moves; 50 L/s is 180 cubic metres an hour.
The acceptable solution explains why the fans are there. In its own words, natural ventilation on its own isn’t adequate to remove moisture generated from cooktops, showers and baths. It also notes that an extract fan clears moisture at the source and won’t necessarily ventilate the whole room. Opening windows have to be able to stay fixed open, so a gust can’t slam them shut.
One more line catches people out. A kitchen, bathroom, toilet or laundry with no external wall must be mechanically ventilated under the mechanical or combined routes. An internal ensuite with no window isn’t a problem, provided the fan and its duct are designed in.
What doesn’t count as ventilation
Several common assumptions fail the Code. BRANZ, the building research body, points out in its Bulletin 698 on residential mechanical ventilation that because G4 asks for outdoor air, a system that draws its air from the roof space can’t be used to show compliance with G4. The roof space isn’t outdoors, whatever the brochure says about filtered, warmed air.
A recirculating rangehood, which filters cooking air and blows it back into the kitchen, doesn’t extract moisture and, per the same bulletin, doesn’t meet G4/AS1. Extracted air should always go outside, never into the roof space, where it condenses and feeds mould. And a heat pump, for all its indoor and outdoor units, brings in no fresh air at all. BRANZ is blunt about it: a house heated by heat pumps still needs effective ventilation.
💡 Homeowner tip: When you choose a rangehood, check two things on the spec sheet: that it’s ducted to the outside (not recirculating) and that its extract rate is at least 50 L/s. A hood that looks right on the showroom wall can fail both.
Units with only one outside wall
G4/AS1 has a separate set of rules for household units with only one external wall that has opening windows, the layout of many apartments and some infill units. There, each kitchen, bathroom, toilet, laundry and habitable room on the outside wall needs either openings of at least 5% of its floor area or high-level trickle ventilators, and the room must measure less than 6 metres from the external wall to the opposite wall. A trickle ventilator is a small closable vent to the outside, usually built into the window frame, and the acceptable solution sets a minimum opening of 2,000 mm² for each one.
A habitable room with no opening of its own, such as a bedroom tucked behind a living room, can be ventilated through the next room only under tight conditions. The two rooms together need openings of 5% of their combined floor area, high- and low-level trickle vents, a permanent opening between them of 5% of the combined area, and a combined depth under 6 metres. The neighbouring room can’t be a kitchen, bathroom, toilet or laundry. The cooktop, shower and bath extract rates still apply.
BRANZ’s article on airtight homes notes that attached dwellings, which often have only two external walls, are the ones most prone to overheating and limited ventilation options. If you’re designing a terrace or a unit on a tight section, the ventilation strategy shapes the floor plan, not just the services.
None of this means windows and fans are a poor design. For many Auckland homes they’re the right answer. The question is what happens once the house is so well sealed that the windows are doing all the work.
Why an airtight home outgrows the minimum
A rule written for draughty houses
The 5% window rule has a long history. BRANZ notes in Bulletin 698 that it’s unchanged from regulations that existed in 1947, and that it assumes a certain amount of air leaks in through the building itself. That leakage, called infiltration, is the uncontrolled air that finds its way through gaps around floors, windows, ceilings and chimneys.
A 1920s villa in Grey Lynn gets plenty of it. Gaps in the floorboards, an open chimney and loose sash windows replace the air whether anyone opens a window or not. The same BRANZ bulletin shows average infiltration falling steadily by decade of construction, and says New Zealand homes have become much more airtight as building materials and methods changed.
The standard behind the mechanical route shows the same age. G4/AS1 refers to NZS 4303:1990, the New Zealand Standard for ventilation and indoor air quality, for mechanical ventilation rates. BRANZ notes that standard says ventilation is normally satisfied by infiltration and natural ventilation, and adds that the statement is unlikely to hold for homes being built today.
What airtight means, and how it’s measured
Airtightness is how much air moves through the building fabric itself. It’s tested with a blower door, a fan fitted into an external doorway that holds the house at a steady pressure difference of 50 pascals (Pa) and measures how much air it takes to keep it there. The result is quoted in air changes per hour at 50 Pa, which says how leaky the envelope is, not how much fresh air the occupants get.
There is no airtightness target in the New Zealand Building Code or its standards. BRANZ says so plainly, and notes that testing here is usually done on homes chasing an environmental or performance certification. So a new home can be very tight without anyone having measured it. BRANZ’s article Build tight and ventilate right adds that air infiltration measured in real houses is well below what blower door results would suggest, and that infiltration shouldn’t be relied on for fresh air.
How much fresh air a house actually needs
Guidelines quoted by BRANZ put a healthy ventilation rate for a home at 0.35 to 0.5 air changes per hour. In plain terms, a third to a half of the air inside is swapped for outdoor air every hour. NZS 4303 sets 0.35 for living areas in private dwellings.
You can turn that into a number for your own plans. BRANZ’s worked example takes a 120 m² house with an internal volume of 288 m³: multiply by 0.35 and the house needs about 100.8 m³ of fresh air an hour. Its second example, a 250 m² house of 675 m³, needs about 236 m³ an hour. Watch the units when you compare system specs, because one litre per second equals 3.6 m³ an hour, and BRANZ says it has seen the two confused.
Why the windows stay shut
In a tight house, that fresh air arrives only when someone opens a window. BRANZ’s research says opening windows fully for just 15 minutes a day can significantly reduce indoor moisture. The catch is people. BRANZ lists the reasons windows stay closed: security, noise, the fear of losing heat and the cost of reheating, and plain lack of awareness. BRANZ adds that the comfort cost makes window-opening less likely in the colder months, which is when a closed-up Remuera bedroom collects moisture from breathing and from washing dried indoors.
That’s why Bulletin 698 goes beyond the Code minimum. BRANZ recommends mechanical ventilation as the default option to achieve 0.35 to 0.5 air changes per hour, and says ventilation in a new build should be considered from the very start of design, not added later. If you’re planning a new home, that’s the moment our team uses to design a new home around its services from day one, ventilation included.
💡 Homeowner tip: Ask your designer early whether the house is likely to be tested for airtightness. If you’re aiming for a tested, very tight envelope, plan whole-house ventilation into the concept rather than relying on window habits.
Heat recovery ventilation compared with the other systems
BRANZ describes three families of mechanical ventilation for houses. They differ in which way the fan pushes air, where that air comes from and whether any heat is kept.


Extract systems
Extract ventilation pulls moist or polluted air out, usually from kitchens and bathrooms. The intermittent version is the bathroom fan wired to the light switch and the rangehood over the cooktop, which every new home on the window route already has. BRANZ suggests a fan linked to the light with a run-on timer, wiring that still lets the fan run without the light, or a humidity sensor.
Continuous extract systems run all the time and keep the house at slight negative pressure, which draws outdoor air in elsewhere. In a new, relatively airtight home they need make-up air from trickle vents in the window frames or vents through the walls. BRANZ warns they may not suit some villas or bungalows, because damp air from under the floor can be drawn up through the gaps. Negative pressure also matters if the house has a gas appliance that takes its air from the room: our guide to the gasfitting rules for a mechanically ventilated house explains why that changes how the gas work is classed.
Supply-only, or positive pressure, systems
A supply system blows air into living areas through ceiling diffusers, keeping the house at a slight positive pressure that pushes stale air out through gaps. BRANZ notes that for this to work the envelope has to let enough air leak out to match the supply, so in a very airtight home a window may need to stay ajar or vents be fitted.
The make-or-break detail is the air source. Some proprietary systems take air from the roof space, some from outside, and some switch to an eaves inlet in warm months. Only outdoor air meets G4, so ask exactly where the intake sits. BRANZ also flags that an intake through the roof is a weathertightness risk unless it’s very carefully detailed, and that a system should never draw roof-space air under cladding where asbestos has been found.
Balanced heat recovery
A balanced heat recovery system has two fans and two sets of ducts: one brings fresh air in from outside, the other takes stale air out. The two streams pass each other in a heat exchanger, so the outgoing warm air pre-warms the incoming cold air without the two mixing. In summer most units can bypass the exchanger and simply ventilate. You’ll also see it called mechanical ventilation with heat recovery, or MVHR.
BRANZ calls a well-designed and commissioned balanced system the best option for whole-house ventilation, with a catch: it has the highest upfront purchase and installation cost. It also says the systems are best for houses with at least moderate airtightness where every space the unit serves is heated. In a leaky house the heat simply escapes through the gaps instead of through the exchanger.
What the testing and modelling showed
The headline efficiency figure needs reading carefully. BRANZ says the heat exchanger itself can reach about 90%, but its testing found whole systems usually perform below that. One deliberately unbalanced system dropped from 70% efficiency in the core to around 40% overall. Ducts and an exchanger outside the insulated part of the house have, in BRANZ’s words, a significant negative impact on performance.
When it works, the payoff is real. BRANZ modelled a 90 m² Wellington house kept at 20°C through July: in the more airtight versions, a heat recovery system at around 55% efficiency roughly halved the heating cost compared with no heat recovery, and at 90% the cost fell to a quarter or less. That’s a model of one house in one month, not a promise for yours, but it shows why airtightness and heat recovery are designed together.
Designing heat recovery ventilation into the plans
If you decide on a heat recovery system, most of what makes it work or fail is decided on paper. These are the items we settle in the drawings rather than leaving to the installer on site.
Where the unit and the ducts go
BRANZ’s guidance is that the ducts should ideally sit inside the thermal envelope, the insulated shell of the house. One way is a warm roof, where the insulation follows the roof slope so the ceiling space above the rooms stays on the warm side. Where ducts can’t stay inside, BRANZ says they must be well insulated, above R1.5 (the R-value measures how well insulation resists heat flow), because an uninsulated roof void can be far colder than the air in the duct.
That choice shapes the house. A warm roof changes the roof build-up and its details. Ducts inside the envelope may need a bulkhead or a dropped ceiling along a hallway, which affects ceiling heights and lighting. BRANZ also wants duct runs as short as possible, with smooth insides and as few bends as possible, so the unit’s location in the plan matters as much as the unit itself.
Intakes, exhausts and condensate
G4/AS1 requires outdoor air intakes to be placed so they avoid contamination from any local source. In practice that means keeping the intake clear of the rangehood and bathroom exhausts, a gas flue, the bin store and the driveway, and on a tight Hobsonville or Flat Bush section, clear of the neighbour’s outlets too. BRANZ adds that exhaust air should discharge where it won’t re-enter the fresh air supply, be drawn back in through a window or door, or enter another dwelling.
The exchanger produces water when it pulls heat out of the stale air. BRANZ calls for a condensate drain from the exhaust side, with ducts falling at around 2% to that drain where condensation is a risk. The drain needs a route to a waste pipe, which is one more reason the unit’s position belongs on the plan rather than in a gap someone finds later.
💡 Homeowner tip: Ask for the ventilation unit, the duct routes, the intake and the exhaust terminals to be shown on the drawings. If they only appear in a supplier quote, nobody has checked them against the structure, the insulation or the neighbours.
Wet rooms and the kitchen on an outside wall
Even with whole-house ventilation, the kitchen and bathrooms carry the heaviest moisture loads, and G4/AS1 still sets the extract rates for them. Planning helps here. Putting wet rooms and the cooktop on an external wall gives short, straight duct runs for the rangehood and fans, which suits BRANZ’s advice on short runs with few bends. G4/AS1 itself reminds designers that extract ducts passing through fire-rated building elements must keep the fire performance of those elements, which matters in an attached unit or a terrace.
Commissioning and the maintenance you sign up for
A heat recovery system is set up after it’s installed, a step called commissioning. G4/AS1 says commissioning of mechanical systems must follow CIBSE Code Series A, a UK commissioning code, and BRANZ says commissioning should check the system matches the plans and the maker’s requirements, that ducts are connected and sealed, and that the inflow and outflow are balanced. BRANZ suggests a third party, not the installer, ideally does it.
Then there’s upkeep, which G4 itself requires: mechanical systems must be maintained so bacteria and allergens don’t build up. BRANZ lists replacing filters as the maker recommends, cleaning outside hoods and screens about every 12 months, cleaning condensate drains and pans, and checking roof-space ducts for damage every two years. If that schedule doesn’t suit how you live, it’s a reason to choose a simpler system.
Our performance design that plans the ventilation from the first sketch covers these decisions alongside insulation, glazing and heating, because each one changes the others.
Important: Ventilation is part of the building consent for a new home or extension, whether it follows G4/AS1 or an alternative design. Whether your particular system, or a change to it during the build, needs consent or an amendment is for Auckland Council to decide. Talk to your designer, a Licensed Building Practitioner or Auckland Council before you buy or install anything.
Extensions and renovations: joining new rooms to an older house
What the Building Act asks of the existing house
New building work must comply with the Building Code: section 17 of the Building Act says so whether or not a consent is needed. So a new kitchen, bathroom or bedroom in an extension needs G4-compliant ventilation, including the extract fans.
The existing house is treated differently. Under section 112, the council can’t grant consent for an alteration unless, afterwards, the building keeps complying with the Code if it complied before, or complies at least as well as it did if it didn’t. An extension can’t make the existing rooms worse. Closing in a window that used to ventilate a bedroom, or turning a laundry with an outside wall into an internal one, can trip that test.
Airtight extension, draughty villa
Picture a 1950s brick-and-tile bungalow in Howick getting a new open-plan kitchen and living wing. Going by BRANZ’s figures on how much tighter houses have become decade by decade, the new wing is likely to be far tighter than the house it joins. The new kitchen and bathroom still need extract fans ducted outside, exactly as in a new build, because the new work has to meet G4 on its own.
Whole-house heat recovery in a part-new, part-old house is harder. BRANZ says balanced systems are best where airtightness is at least moderate and every room served is heated, so ducting it into a leaky villa wing can lose much of the benefit. For an extension, a sensible starting point is properly sized, ducted extract in the new wet rooms and kitchen, with whole-house ventilation considered once the existing house’s gaps, insulation and heating are on the table. That’s the kind of extension design that ties new rooms into an older house without leaving the old rooms worse off.
Fix the moisture source first
If the reason you’re looking at ventilation is condensation or mould, BRANZ’s advice is to find and deal with the sources before reaching for a system. In an older house that often means a damp subfloor, missing insulation, unflued gas heaters, a dryer not vented outside, or washing dried indoors. Its bulletin says that when retrofitting ventilation into an older house, you should also look at insulation, heating and gaps in the thermal envelope.
💡 Homeowner tip: If the house or a granny flat on the section is rented, the Healthy Homes ventilation rules for landlords apply on top of the Building Code. Superior Property Services covers those in its guide to ventilation systems in Auckland rentals.
Rooms in an older house that people sleep in, cook in or dry clothes in are where this matters most. Get the extract right there first, and any whole-house system you add later has a sound base to work from.
Getting the ventilation right before the drawings are done
Heat recovery ventilation is a choice, not a Code requirement. Section 18 of the Building Act says the Act doesn’t require anyone doing building work to meet performance criteria beyond the Code’s, so windows plus properly ducted extract fans remain a compliant way to ventilate a new Auckland home. What changes the answer is how tight the house is and how you’ll live in it. If the envelope is airtight and every room is heated, a balanced system designed into the plans earns its place. If not, good extract and opening windows that people will actually open may be the better spend.
Either way, the time to decide is before the consent drawings. Once the ceiling, the roof build-up and the wet rooms are fixed, the ventilation has to fit around them. The phone number is 0800 272 469 if you’d rather talk it through.
➡ Book a free consultation with Sonder Architecture
➡ Request your free feasibility report
➡ Plan ventilation into a new home or extension with our design team
➡ See recent projects we’ve done across Auckland
Is heat recovery ventilation required in a new NZ home?
No. Building Code clause G4 requires ventilation with outdoor air but names no system. Under Acceptable Solution G4/AS1, opening windows of at least 5% of each space's floor area, plus extract fans of 25 L/s for showers and baths and 50 L/s for cooktops ducted outside, meet the Code. Section 18 of the Building Act says the Act doesn't require anyone doing building work to go beyond the Code, so heat recovery is a design choice.
What does G4 ventilation actually require?
Clause G4 requires spaces to have ventilation with outdoor air that keeps the air pure, a way to remove cooking fumes, moisture from bathing and laundry, and combustion products, and mechanical systems maintained so bacteria and allergens don't multiply. It also requires enough air for any fixed fire or gas appliance that draws air from the room. The acceptable solution G4/AS1 shows one accepted way to meet it.
Which edition of G4/AS1 applies to my consent?
The fifth edition, published by MBIE on 28 July 2025. MBIE's information sheet says the fourth edition could be used to show compliance only until 31 July 2026. The fifth edition mostly changed layout and references; the 5% openable window rule and the 25 L/s and 50 L/s extract rates are still there.
Does a positive pressure system that uses roof space air meet the Building Code?
Not on its own. G4 asks for ventilation with outdoor air, and BRANZ's Bulletin 698 says systems drawing air from the roof space cannot be used to demonstrate compliance with G4. Some systems can take outside air instead, or switch to an eaves inlet in warmer months. Check exactly where the intake sits before relying on a system for ventilation.
How much fresh air does a house need?
BRANZ cites guidelines of 0.35 to 0.5 air changes per hour, meaning a third to a half of the air inside replaced by outdoor air each hour. NZS 4303 sets 0.35 for living areas in private homes. BRANZ's example: a 120 m² house with 288 m³ of internal volume needs about 100.8 m³ of fresh air an hour at 0.35.
Is there an airtightness requirement for new houses in New Zealand?
No. BRANZ states there is no requirement to meet a particular airtightness level in the Building Code or standards. Airtightness is tested with a blower door at a 50 pascal pressure difference, and in New Zealand testing is usually done on homes seeking an environmental or performance certification. New homes are still much tighter than older ones, which is why ventilation matters more.
How efficient is heat recovery ventilation?
BRANZ says the heat exchanger itself can reach about 90%, but its testing found whole systems usually perform lower. A deliberately unbalanced system dropped from 70% in the core to around 40% overall, and ducts or an exchanger outside the insulated envelope cut performance significantly. Design, balancing and commissioning decide how close a real system gets.
Do I need a rangehood that vents outside?
Under G4/AS1, a space with a cooktop needs mechanical extract of at least 50 L/s, exhausting to the outside. BRANZ notes that a recirculating rangehood, which filters air and returns it to the kitchen, doesn't remove moisture and doesn't meet G4/AS1. Extracted air should never be dumped into the roof space, where it can cause condensation and mould.
Does a heat pump ventilate my house?
No. BRANZ points out that heat pumps, despite their indoor and outdoor units, bring no fresh air into a home and provide no ventilation. A house heated by heat pumps still needs opening windows and extract fans, or a mechanical ventilation system, to meet G4 and control moisture.
Can I add heat recovery ventilation to an extension on an older house?
You can, but it works best where the house is reasonably airtight and every room it serves is heated, according to BRANZ. In a part-new, part-old house, ducted extract in the new kitchen and bathrooms is the usual starting point. Under section 112 of the Building Act, the extension also can't leave the existing house complying less well than before. Talk to your designer or Auckland Council about consent.
Related guides
- getting sun, shade and cross-breezes right in an Auckland home
- how insulation compliance works under H1 now
- what it takes to add a bathroom or toilet to your home
References
- Building Regulations 1992, Schedule 1, clause G4 Ventilation
- MBIE, Acceptable Solution G4/AS1 Ventilation of buildings, fifth edition (28 July 2025)
- MBIE, Get to know G4/AS1 Fifth edition (information sheet)
- Building Act 2004, sections 17, 18, 19 and 112
- BRANZ, Bulletin 698: Residential mechanical ventilation systems (March 2025)
- BRANZ, Build tight and ventilate right